alert alert - HubSpot

0 downloads 322 Views 590KB Size Report
AC Interrupt Rating. 200kA. 300kA. 300kA. 300kA (200kA 70-100A). DC Interrupt Rating. NA. 50kA. 20kA. 100kA. Amperage Ra
EATON BUSSMANN

FUSE SAFETY

ALERT

Eaton Bussmann identified a potential nonconformance due to exposed wires in Bussmann series CUBEFuses which may contain a safety hazard.

Protect your workers with Littelfuse Class J Fuses.

Eaton Bussmann Series CUBEFuse Safety Hazard According to a Product Safety Bulletin issued January 12, 2018, Eaton has identified a potential nonconformance in its Bussmann series CUBEFuses that may result in an exposed, 42 AWG wire (0.07 diameter) used in the indicating circuit of the CUBEFuse. The Bulletin reports that the indicating wire may be exposed to the front or back of the fuse, thereby eliminating its reported finger safe characteristics. The Bulletin warns that the failure to wear appropriate personal protective safety equipment (“PPE”) when servicing these fuses poses a safety risk and can cause personal injury, death or property damage. This is an important potential safety hazard. When servicing these fuses, proper PPE must be worn to ensure your workers’ safety. View Product Safety Bulletin

Littelfuse Class J Fuses are a Safety Solution In most applications, Littelfuse Class J fuses can be safely installed as a replacement for Eaton Bussmann series CUBEFuses. Littelfuse JTD-ID indicating circuits are fully internal as part of the fuse construction and offer no danger of exposed wires. JTD Product Advantages ■■ Internal circuits – No Danger of Exposed Wires ■■ 50 Ratings from 8/10A – 600A ■■ Superior operating temperature range ■■ Exceptional short circuit current limitation ■■ Excellent watts loss performance ■■ Readily available, standard distribution ■■

Low cost, high performance, high quality

Protect your workers and install a safety solution from Littelfuse.

EATON BUSSMANN

FUSE SAFETY

ALERT

Swap Out Danger Recommended Step-By-Step Guide for swapping out Eaton Bussmann series CUBEFuses with Littelfuse Class J Fuses WARNING: In all instances, to protect worker safety, appropriate personal protective safety equipment must be worn. Hazardous voltages may be present; be sure power is disconnected prior to swap out. Swap out should be done by qualified personnel following all national, state, and local codes.

DIN-Rail Mounted (30A & 60A) To remove the CUBEFuse: 1. One end of the Bussmann holder has a spring. Pull down on the holder to remove it from the bottom of the DIN rail. 2. Position the holder at an angle. 3. Lift up to remove the top side from the DIN rail.

To install the Littelfuse fuseholder: 1. Pull down on the red DIN release tab(s) to the open position. 2. Place the fuseblock onto the DIN rail. 3. Push the DIN release tab(s) to lock over the bottom of the DIN rail.

Screw Mounted To remove the CUBEFuse: 1. Remove the center mounting screw (30A and 60A) or two screws on opposite sides (100A). 2. Remove fuseblock from the panel. 

To install the Littelfuse fuseholder (30A & 60A): 1. Line up the hole on the CUBEFuse holder with the slot on the Littelfuse holder. 2. Screw in fuse holder.

30A

LITTELFUSE

To install the Littelfuse fuseholder (100A): 1. Measure for new drill holes. 2. Drill new holes for the slots on the Littelfuse holder. 3. Screw in fuse holder.

60A

BUSSMANN

LITTELFUSE

100A

BUSSMANN

LITTELFUSE

BUSSMANN

EATON BUSSMANN

FUSE SAFETY

ALERT

Competitive Comparison Chart Littelfuse

Bussmann

Littelfuse

Bussmann

Family

JLS

FCF

JTD

TCF

Product Type

Fast Acting

Fast Acting

Time Delay

Time Delay

UL Class

J

CF

J

CF

Indicating Option

No

Yes

Yes

Yes

AC Voltage Rating

600

600

600

600

DC Voltage Rating

NA

600

300

300

AC Interrupt Rating

200kA

300kA

300kA

300kA (200kA 70-100A)

DC Interrupt Rating

NA

50kA

20kA

100kA

Amperage Range

1A - 600A

1A - 100A

0.8A - 600A

1A - 100A

Total Amperage Ratings Available Up to 100A

17

17

37

18

Operating Temp. Range

-55 to 125C

-40 to 80C

-55 to 125C

-40 to 80C

Body

Melamine

Thermoplastic

Melamine

Thermoplastic

Termination

Nickel plated bronze to 60A, brass 70-100A

Tin plated copper alloy

Nickel plated bronze to 60A, brass 70-100A

Tin plated copper alloy

UL Listed

Standard 248-8, Class J (File: E81895)

Guide JFHR (File: E4273)

Standard 248-8, Class J (File: E81895)

Guide JFHR (File: E4273)

CSA Certified

File: LR29862

Class 1422-02, File 53787 File: LR29862

Watts Loss JTD 4.25W 6.45W 7.46W

30A 60A 100A

TCF 3.99W 6.23W 9.51W

30A 60A 100A

Class 1422-02, File 53787

Total Clearing I2 t @200kA JTD TCF 4754 Not Published 10450 Not Published 68150 Not Published

Cross Reference Bussmann

Equivalent Littelfuse Combination Fuseblock + Cover

CUBE Fuse Rating

Fuse Holder

Class J Fuse Rating

Fuse Block

Optional Cover

FCF / TCF 0 - 30A

TCFH30N

JLS / JTD 0-30A

LFJ60030 series

LFJ60030FBC

FCF / TCF 35 - 60A

TCFH60N

JLS / JTD 35-60A

LFJ60060 series

LFJ60060FBC

FCF / TCF 70 - 100A

TCFH100N

JLS / JTD 70-100A

LFJ60100 series

LFJ60100FBC

Equivalent Littelfuse Dead-Front Holder Class J Fuse Rating

Fuse Holder

JLS / JTD 0-30A

LFPSJ30 series

JLS / JTD 35-60A

LFPSJ60 series

JLS / JTD 70-100A

Not Available

Littelfuse.com

Web Resource Links JLS Fuse Datasheet JTD Fuse Datasheet LFJ Series Fuseholder Datasheet LFPSJ Fuseholder Datasheet Eaton Bussmann Product Safety Bulletin

© 2018 Littelfuse POWR-GARD® Products